Huawei 25KW half-cabinet inverter air-cooled air conditioner, the following description is correct (multiple choice)
A. The capacity algorithm for a single air conditioner with UPS is 1.2* 1.732*full load current*380*0.8/0.9
B. The capacity algorithm for a single air conditioner with UPS is 1.2*5* 1.732*full load current*380*0.8/0.9
C. The UPS capacity requirement of a single air conditioner is 15.8kVA. If you configure UPS5000E, you need to configure at least one 25kVA power module
D. The UPS capacity requirement of a single air conditioner is 79.0kVA. If you configure UPS5000E, you need to configure at least two 40kVA power modules
E. If a group of air conditioners is connected to a set of UPS systems, then it is necessary to multiply the number of air conditioners running at the same time on the basis of a single UPS, such as 5+1 cold backup configuration, then it needs to be based on the capacity requirement of a single air conditioner UPS Multiply by 5 to get total UPS capacity requirement, configure
Notifications
Clear all
Topic starter
Suggested Answer: A,C,E
Posted : 05/01/2023 3:50 am